75
Result:
Factor
=4447
Calculate
log1_Ana Offset
according to the required offset voltage:
8191/10 log1_ /
shift
v Ana Offset U
Result:
log1_Ana Offset
=819
The following changes are required on the basis of Example 7-3.
Table 7-14 Parameter settings in Example 7-5
d3.24
Analog1_Offset
Sets offset data for
external analog signal 1
Set to 819
d3.29
Analog_Speed_Factor
Sets the proportion
between analog signals
and output speed
Set to 4447
d3.00
Store_Loop_Data
1: Storing all configured
parameters for the
control loop
10: Initializing all
parameters for the
control loop
Set to 1
Example 7-6: Analog speed mode (setting the dead zone voltage and
offset voltage)
Requirement: Set the offset voltage to 1V, the dead zone voltage to 0.5V to 1.5V, and the max speed
corresponding to 10V to 3000 rpm. Select analog channel 1 (AIN1) to control the speed.
Fig. 7-12 Schematic diagram of Example 7-6
Calculate
filter
U
according to the offset voltage and dead zone voltage that require settings:
2047
10 10
filter
shift dead
U
v v U U

(In this example,
0
dead
U
.5, and
1
shift
U
)