EasyManua.ls Logo

Kramer VS-1616A - Control Interface Connections; Connecting a Control Interface

Kramer VS-1616A
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KRAMER: SIMPLE CREATIVE TECHNOLOGY
Installing the Balanced Stereo Audio Matrix Switcher
18
Refer to section 8.2 for a description of the MENU’s Follow-SYSTEM
and Breakaway-from- SYSTEM modes.
6.6.4 Understanding the SLAVE Mode
The SLAVE mode is only used for the multi-channel audio switcher
configuration
2
Figure 6
, for example, when using 2 VS-1616A units to form a
4-channel 16x16 configuration, as illustrates.
One unit is used as the Master, and the other unit is a Slave. The Slave
always follows the Master. In the example illustrated in
Figure 6, the first
VS-1616A unit is the Master (with DIP 6 set OFF disabling the Slave
mode) and the second VS-1616A unit is a Slave (with DIP 6 set ON
enabling the Slave mode).
On the Slave VS-1616A unit, the MATRIX and STATUS Displays do
not illuminate and the STATUS Display shows the following message:
Keyboard LOCKED
However, the STATUS Display on the Slave VS-1616A unit dynamically
shows
3
Front panel control is via the Master VS-1616A unit, on which the front
panel buttons are unlocked and both the MATRIX and STATUS Displays
illuminate.
all changes made from the Master VS-1616A unit.
6.7 Connecting a Control Interface
Connect a control interface (RS-232 or RS-485) unless operating a
VS-1616A as a standalone unit without any control device (that is, with
control from the front panel or IR port, and not via a remote controller or
a PC). The control interface must be identical on each switcher in the
series of 16x16 matrix switchers; either RS-232 or RS-485. One control
interface suffices. Do not use both RS-232 and RS-485 control interfaces
in the same configuration. For example, in an interconnected varied-
format 16x16 switcher application
4
1 See section
, if the switcher that connects to the
PC connects via the RS-232 control interface, each switcher must
interconnect via the RS-232 control interface and not via the RS-485
control interface.
6.5
2 See section
6.1
3 Albeit with an LCD Display that does not illuminate
4 See section
6.5

Table of Contents

Related product manuals