6 Installation at Site
18 of 44
Hya-Solo DSV
protection device, this device is connected to digital input 1 (C1 and C2).
The functions of digital inputs 2 to 5 can be parameterised by the user at the control
panel. To connect the inputs use terminal C1 (+24VDC).
For setting the parameters see the PumpDrive2 operating manual.
6.7.4 Relay outputs
Terminal strip A, terminals A1 to A10
In as-delivered condition the relay outputs are parameterised as volt-free contacts for
"Alarm" (relay1) and "RUN operating status" (relay2). Different messages can be
assigned to these relay outputs via the control panel.
For setting the parameters see the PumpDrive2 operating manual.
6.7.5 Analog inputs
Terminal strip B, terminals B1 to B8
Analog input1 can be connected to an external setpoint adjustment.
Analog input2 is assigned to the pressure transmitter (feedback value transmitter) as
standard and connected to the mains-motor-PTC terminal strip.
For setting the parameters see the PumpDrive2 operating manual.
6.7.6 Analog output
Terminal strip B, terminals B9 and B10
PumpDrive features an analog output whose output value can be parameterised via
the control panel depending on the digital inputs.
For setting the parameters see the PumpDrive2 operating manual.