8 Diagnosis
1024 Error while reading
received XML data
An XML document
received from the external
system does not corre-
spond to the XPath
schema.
Check the XML document
sent by the external sys-
tem.
1280 Limit of element storage
reached
The data memory is
assigned the maximum
number of data elements.
The Ethernet connection is
closed.
Evaluate the return value
of the EKI_Get…() function
in the KRL program to dis-
able the processing of
received data ("Buff" ele-
ment).
(>>> 6.2.7 "EKI_STATUS
– Structure for function-
specific return values"
Page 35)
OR
Increase the data memory
(BUFFERING element in
the connection configura-
tion).
1536 Received string too long Programming error on
external system: a string
received from the external
system exceeds the maxi-
mum permissible length
(max. 3,600 characters).
Check the data sent by the
external system.
1792 Limit of element memory
reached
The data memory is
assigned the maximum
number of bytes. The
Ethernet connection is
closed.
Increase the data memory
(BUFFSIZE element in the
connection configuration).
2048 Server time limit reached Server is waiting for a call. Check external system.