8: Setup Mode: Channel Configuration
UDS2100 Device Server User Guide 47
Table 8-3. Flow Control Options
No flow control
XON/XOFF flow control
Hardware handshake with RTS/CTS lines
XON/XOFF pass characters to host
Port Number
The setting represents the source port number in TCP connections. It is the
number that identifies the channel for remote initiating connections.
Port No (10001) ? _
The default setting for Port 1 is 10001. The range is 1-65535, except for the
following reserved port numbers:
Table 8-4. Reserved Port Numbers
Warning: We recommend that you not use the reserved port
numbers for this setting as incorrect operation may result.
Use Port 0 for the outgoing local port to change with each connection. The port
range is 50,000-59,999. Each subsequent connection increments the number by
1 (it wraps back around to 50,000).
Only use this automatic port increment feature to initiate a connection using TCP.
Set the port to a non-zero value when the unit is in a passive mode or when
using UDP instead of TCP.
Connect Mode
Connect Mode defines how the unit makes a connection, and how it reacts to
incoming connections over the network.
ConnectMode (C0) ? _
Enter Connect Mode options in hexadecimal notation. The default setting is C0.
Note: All bit positions in the table that are blank represent “don’t care” bits
for that particular option, which can be set to either a 0 or 1 value.
Reserved (well known ports)
9999
14000-14009
30704
30718