EasyManua.ls Logo

Lauda ECO GOLD - RS 485 Protocol; Libus Module

Default Icon
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
09/2021 ECO Gold 115 / 134
An RS 485 bus requires essentially a bus termination in the form of a terminating network, which provides a defined idle
state in the high impedance phases of bus operation. The bus termination is as follows:
Generally, this terminating network is integrated on the PC plug-in card (RS 485).
19.3.4 RS 485 protocol
Note the following aspects:
The interface operates with one stop bit, no parity bit and with eight data bits.
Transfer speed alternatively: 2400, 4800, 9600 (factor setting) or 19200 baud.
The device address always precedes the RS 485 commands. Up to 127 addresses are possible. The address
must always consist of three figures
(A000_... to A127_...).
The command from the computer must be terminated with a CR.
The response from the thermostat is always terminated with a CR.
CR = Carriage Return (Hex: 0D)
Example:
Set-value transfer of 30.5 °C to the thermostat with address 15.
Computer
Thermostat
„A015_OUT_SP_00_30.5“CR
„A015_OK“CR
19.4 LiBus module
LiBus module (catalogue number LRZ 920) has a socket (70S) for connec-
ting components via the LAUDA device bus LiBus (Command remote con-
trol, shut down/reverse flow protection, cooling water valve).
LiBus = LAUDA internal device BUS (CAN-based)
For extension cord for LiBus, see accessories ( 9)

Table of Contents

Other manuals for Lauda ECO GOLD

Related product manuals