iComfort Wi-Fi
®
7-Day Programmable Communicating Thermostat
Page 11
Table 5. System Devices > Air Handler
System
Heat Pump
Air Handler
Thermostat
system devices
To adjust a setting,
highlight it, then press
Edit
edit
next
back
about
resetAll
Air Handler
Parameter Name: Default Parameter Value Setting Increment
Equipment Name Air Handler
Press edit to change name (up to 35
characters may be used).
Note: Pressing the resetALL button will
reset all custom parameter settings back
to factory default.
—
Electric Heating Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
5CFM
High Cooling Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
5CFM
Airflow Profile - Cooling 1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min;
OFF:50%/30s
—
Continuous Indoor Blower Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
10CFM
Heating Indoor Blower OFF Delay 10 sec 0 to 10 Seconds 1 sec
Heating Indoor Blower ON Delay 0 sec 0 to 5 Seconds 1 sec
Cooling Indoor Blower OFF Delay 0 sec 0 to 30 Seconds 2 sec
Cooling Indoor Blower ON Delay 2 sec 0 to 10 Seconds 1 sec
Note All communicating Installer Parameters default CFM values based on DIP switch setting (non-communicating value) are calculated using the CFM
conversion tables and rounded up to closest number on 25 CFM resolution.