iComfort Wi-Fi
®
7-Day Programmable Communicating Thermostat
Page 47
Table 10. Alert Codes and Troubleshooting
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
Alert
Code
PRIORITY
CONDITION
APPLICABLE
SYSTEM
COMPONENTS
ALERT TEXT
COMPONENT OR SYSTEM OPERA
TIONAL STATE AND TROU
BLESHOOTING TIP
HOW TO CLEAR
ALERT CODE
114
Moderate /
Critical
Furnace, air han
dler, equipment in
terface or IHarmo
ny damper control
module
There is a frequency / distortion
problem with the power to a
specific system component.
This alert code may indicate
transformer overloading.
Check the voltage and line power
frequency.
Check the generator operating
frequency, if the system is run
ning on back-up power.
Correct voltage and frequency
problems.
System will resume normal oper
ation five seconds after fault re
covered.
All applicable system component
outputs are disabled – moderate
condition.
After 10 minutes, the priority con
dition is escalated – critical con
dition.
Damper control module will oper
ate in central mode only until
proper voltage is restored or fre
quency distortion is resolved –
moderate condition.
Automatically clears
when the system de
tects the issue no
longer exists.
115 Critical
Furnace, air han
dler or equipment
interface module
Primary 24VAC power to a sys
tem component control is lower
than the required range of 18 to
30VAC.
Primary 24VAC voltage is low
(range is 18 to 30 volts).
Check and correct voltage.
Check for additional power-rob
bing system component (device)
connected to system.
This alert code may require the
installation of an additional or
larger VA transformer.
Automatically clears
when the system de
tects the issue no
longer exists.
115 Critical
IHarmony Damper
control module
Secondary 24VAC power to the
damper control module is low.
Secondary 24VAC voltage is low
(range is 18 to 30 volts).
Check and correct voltage.
Check for additional power-rob
bing equipment connected to sys
tem.
This alert code may require the
installation of an additional or
larger VA transformer.
Damper control module will oper
ate in non-zone mode until proper
voltage is restored.
Automatically clears
when the system de
tects the issue no
longer exists.
117 Minor
Furnace
The reporting unit has poor
earth grounding.
Provide proper grounding for the
system component (device).
Check for proper earth ground to
the system.
Automatically clears
30 seconds after the
issue is corrected.
120 Moderate
Thermostat, fur
nace, air handler,
outdoor unit,
equipment inter
face or IHarmony
damper control
module
There is a delay in the system
component responding to the
system.
Typically this alert code does not
cause any operational issues and
will clear on its own.
This alert code is usually caused
by a delay in the outdoor unit re
sponding to the thermostat.
Check all wiring connections.
Automatically clears
after an unresponsive
system component
(device) responds to
any inquiry.