Table 10. Alert Codes and Troubleshooting
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
Alert
Code
PRIORITY
CONDITION
APPLICABLE
SYSTEM
COMPONENTS
ALERT TEXT
COMPONENT OR SYSTEM OPERA
TIONAL STATE AND TROU
BLESHOOTING TIP
HOW TO CLEAR
ALERT CODE
124 Critical
Thermostat, fur
nace, air handler,
outdoor unit,
equipment inter
face or IHarmony
damper control
module
The thermostat has lost com
munication with a system com
ponent for more than three min
utes.
System component has lost com
munication with the thermostat.
Check the wiring connections.
Ohm wires.
Cycle power.
This alert code stops all associat
ed system operations and waits
for a heartbeat message from the
system component that is not
communicating.
Automatically clears
after communication is
re-established with ap
plicable system com
ponent (device).
125 Critical
Thermostat, fur
nace, air handler,
outdoor unit,
equipment inter
face or IHarmony
damper control
module
There is a hardware problem
on a system component con
trol.
There is a control hardware prob
lem.
Replace the control if the problem
prevents operation and is persis
tent.
Damper control module will re
main in non-zone mode (all
dampers open) for five minutes
after priority condition no longer
exist.
Automatically clears
300 seconds after the
issue no longer exists.
126 Critical
Furnace air han
dler or outdoor
unit
There is an internal communi
cation problem with a system
component.
There is an internal hardware
problem on the system compo
nent control.
Typically the system component
control will reset itself.
Replace the system component
(device) control if the problem
prevents operation and is persis
tent.
Automatically clears
300 seconds after the
issue no longer exists.
130 Moderate
Equipment inter
face module
Air handler jumper is missing.
Configuration jumper missing on
equipment interface module.
NOTE: This is applicable in non-
communicating applications only).
Install the missing jumper.
Automatically clears
after the missing or in
correctly installed
jumper is installed or
corrected.
131 Critical
Thermostat, fur
nace, air handler,
outdoor unit,
equipment inter
face or IHarmony
damper control
module
System component control pa
rameters are corrupted.
Reconfigure the system.
Replace the system component
control if heating or cooling is not
available.
Will automatically clear
when system compo
nent (device) passes
memory self-test or
system component
control is replaced.
132 Critical
Air handler, equip
ment interface
module or IHar
mony damper
control module
System component control
software is corrupted.
Recycle power.
If failure re-occurs, replace the
system component control.
Manual system power
reset is required to re
cover from this alert
code.