Table 10. Alert Codes and Troubleshooting
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
Alert
Code
PRIORITY
CONDITION
APPLICABLE
SYSTEM
COMPONENTS
ALERT TEXT
COMPONENT OR SYSTEM OPERA
TIONAL STATE AND TROU
BLESHOOTING TIP
HOW TO CLEAR
ALERT CODE
412 Moderate
Outdoor unit
The unit high-pressure is above
the required limit.
System is shut down
Unit high pressure is above the
upper limit.
The high pressure switch for
HFC410A will open at 590PSIG
and close at 418PSIG.
Confirm that the system is proper
ly charged with refrigerant.
Check outdoor fan motor, TXV,
indoor unit blower motor, stuck re
versing valve and possible
clogged refrigerant filter.
Confirm that the outdoor unit is
clean.
Automatically clears
after the high pressure
switch closes or a
power reset
413 Critical
Outdoor unit
The high-pressure switch has
opened five times during a sin
gle demand.
Thermostat will shut down the
outdoor unit.
Open high pressure switch error
count reached five strikes.
Check system charge using ap
proach and sub cooling tempera
tures.
Check outdoor fan operation.
Check for dirt or debris blocking
air flow to outdoor unit.
Reset by putting outdoor unit con
trol in test mode or resetting low
voltage power.
Automatically clears
when the system de
tects that the issue no
longer exists.
414 Critical
Outdoor unit
The discharge line temperature
is higher than the recommend
ed upper limit of 279ºF.
Discharge line temperature is
greater than 279ºF.
Make sure coil is clean and air
flow unobstructed in and out of
condenser.
Check system operating pres
sures and compare to unit charg
ing charts in installation manual.
Automatically clears
after discharge tem
perature is less than
225ºF.
415 Critical
Outdoor unit
The discharge line temperature
has been consistently higher
than the recommended upper
limit of 279ºF.
Discharge line high temperature
error count reached five strikes
during a single demand.
Make sure coil is clean and air
flow unobstructed in and out of
condenser.
Check system charge using ap
proach and sub cooling tempera
tures.
Reset by putting outdoor control
in test mode or resetting low volt
age power.
Automatically clears
when the system de
tects that the issue no
longer exists.
416 Critical
Outdoor unit
The outdoor coil sensor is ei
ther open, short-circuited or the
temperature is out of sensor
range.
Outdoor unit control will not per
form demand or time / tempera
ture defrost operation. (System
will still heat or cool.)
Sensor being detected open or
shorted or temperature is out of
sensor range.
Automatically clears
when outdoor unit con
trol detects proper
sensor readings.