2. Properly route and secure the cables in the node. Refer to the cable connecting and routing information
for each component (see
Chapter 6 “Internal cable routing” on page 163).
3. If applicable, reinstall the air baffle (see
“Install an air baffle” on page 70).
4. If applicable, install the top cover onto the node (see
“Install the top cover” on page 160).
5. If necessary, reinstall the node back into an enclosure (see
“Configuration guide” on page 45).
6. If necessary, install any locking devices that secure the top cover, such as a Kensington lock.
7. After checking and making sure that all necessary items are in place, reconnect all external cables and
then the power cords to the server.
Attention: To avoid component damage, connect all the other cables before connecting the power
cords.
8. Power on the server (see
“Power on the server” on page 43).
9. If necessary, reinstall the shipping bracket back into place (see
“Configuration guide” on page 45).
10. Update the server configuration.
Download and install the latest device drivers:
http://datacentersupport.lenovo.com.
Update the system firmware (see
“Update the firmware” on page 177).
Update the UEFI configuration. See
https://pubs.lenovo.com/uefi-overview/.
Reconfigure the disk arrays if you have installed or removed a hot-swap drive. See
https://
pubs.lenovo.com/lxpm-overview/
for the LXPM documentation compatible with your server.
162
ThinkEdge SE350 V2 User Guide