Electrical installation
Mains connection 230 V/240 V
3
EDK82EV113 DE/EN/FR 8.1
101
L
Fuses and cable cross−sections (operation with increased rated power)
Operation without mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K2C 3.0
3/PE AC
100 ... 264 V;
45 ... 65 Hz
M25 A B25 A 4 25 A 10
300 mA
2)
30 mA
3)
E82EV552K2C 5.5
Operation only with mains choke
Operating with mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K2C 3.0
3/PE AC
100 ... 264 V;
45 ... 65 Hz
M20 A B20 A 4 20 A 12
300 mA
2)
30 mA
3)
E82EV552K2C 5.5
M32 A B32 A 6
4)
35 A 8
Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: voltage 240 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for use with E82EVxxxK2C0xx
3)
All−current sensitive e.l.c.b. for use with E82EVxxxK2C2xx
4)
Flexible cable can only be connected using pin end connectors.
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs:
l E.l.c.bs must only be installed between mains supply and controller.
l E.l.c.bs can trip incorrectly because of
capacitive leakage currents of the cable shields during operation (especially with
long, shielded motor cables),
simultaneous connection of several controllers to the mains supply,
use of additional RFI filters.