Electrical installation
Mains connection 400 V/500 V
3
EDK82EV113 DE/EN/FR 8.1
103
L
Fuses and cable cross−section (operation with rated power)
Operation without mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K4C 3.0
3/PE AC
320 ... 550 V;
45 ... 65 Hz
M16 A B16 A 2.5 15 A 14
300 mA
2)
30 mA
3)
E82EV402K4C 4.0
M16 A B16 A 2.5 15 A 14
E82EV552K4C 5.5
M25 A B25 A 4 20 A 12
E82EV752K4C 7.5
M32 A B32 A 6
4)
25 A 10
E82EV113K4C 11
Operation only with mains choke
Operating with mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K4C 3.0
3/PE AC
320 ... 550 V;
45 ... 65 Hz
M10 A B10 A 1.5 10 A 16
300 mA
2)
30 mA
3)
E82EV402K4C 4.0
M16 A B16 A 2.5 15 A 14
E82EV552K4C 5.5
M20 A B20 A 4 20 A 12
E82EV752K4C 7.5
M20 A B20 A 4 20 A 12
E82EV113K4C 11
M32 A B32 A 6
4)
25 A 10
Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C0xx
3)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C2xx
4)
Flexible cable can only be connected using pin end connectors.
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com