3
Electrical installation
Mains connection 400 V/500 V
EDK82EV113 DE/EN/FR 8.1
L
104
Fuses and cable cross−sections (operation with increased rated power)
Operation without mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K4C 3.0
3/PE AC
320 ... 440 V;
45 ... 65 Hz
M16 A B16 A 2.5 15 A 14
300 mA
2)
30 mA
3)
E82EV402K4C 4.0
Operation only with mains choke
E82EV752K4C 7.5
Operation only with mains choke
Operating with mains choke
Installation to EN 60204−1 Installation to UL
1)
8200 vector mains
L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV302K4C 3.0
3/PE AC
320 ... 440 V;
45 ... 65 Hz
M10 A B10 A 1.5 10 A 16
300 mA
2)
30 mA
3)
E82EV402K4C 4.0
M16 A B16 A 2.5 15 A 14
E82EV752K4C 7.5
M25 A B25 A 4 25 A 10
Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C0xx
3)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C2xx
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs:
l E.l.c.bs must only be installed between mains supply and controller.
l E.l.c.bs can trip incorrectly because of
– capacitive leakage currents of the cable shields during operation (especially with
long, shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.