Commissioning
The most important codes for commissioning
7
EDK82EV113 DE/EN/FR 8.1
149
L
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0140* Additive
frequency
setpoint
(NSET1−NADD)
0.00 −650.00 {0.02 Hz} 650.00
l Selection via function of the
keypad or the parameter channel
l Is added to main setpoint
l Value is stored when switching the
mains or removing the keypad
C0148*
Motor parameter
identification
0
0 Ready
Only when the motor is cold!
1. Inhibit controller, wait until drive is
in standstill
2. Enter the correct motor data under
C0087, C0088, C0089, C0090,
C0091 (see motor nameplate).
3. C0148 = set 1 by
4. Enable controller
The identification
starts,
is off
takes approx. 30 s
is completed when
is on
again
5. Controller inhibit
1 Start identification
l V/f−rated frequency (C0015), slip
compensation (C0021) and motor stator
inductivity (C0092) are calculated and
saved.
l The motor stator resistance (C0084) =
total resistance of motor cable and
motor is measured and saved
C0517*
User menu
l After mains switching or when
using the function
the code
from C0517/1 will be displayed.
l In Lenze setting, the user menu
contains the most important codes
for starting−up the control mode
"V/f characteristic control with
linear characteristic"
l When the password protection is
activated, only the codes entered
under C0517 are freely accessible.
l Enter the required code numbers in
the subcodes.
Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!
1 Memory 1 50 C0050 Output frequency (MCTRL1−NOUT)
2 Memory 2 34 C0034 Analog setpoint selection range
3 Memory 3 7 C0007 Fixed configuration − digital input signals
4 Memory 4 10 C0010 Minimum output frequency
5 Memory 5 11 C0011 Maximum output frequency
6 Memory 6 12 C0012 Acceleration time main setpoint
7 Memory 7 13 C0013 Deceleration time main setpoint
8 Memory 8 15 C0015 V/f rated frequency
9 Memory 9 16 C0016 U
min
boost
10 Memory 10 2 C0002 Parameter set transfer