EasyManua.ls Logo

Lenze 8400 BaseLine C - Page 30

Lenze 8400 BaseLine C
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Rated data
Operation at rated mains voltage 400 V
4
30
EDS84ABD302 EN 4.0
Alternative DC supply
Basis of the data
Mains Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f[Hz]
2/PE DC 565 455-0%...620+0% -
Type
Input current at I
aN
Output power
U, V, W
Motor power
4.pol. ASM
I
DC
[A] S
aN
[kVA] P
aN
[kW]
E84AVBxx3714 2.2 0.8 0.37
E84AVBxx5514 2.8 1.1 0.55
E84AVBxx7514 3.6 1.5 0.75
E84AVBxx1124 5.1 2.0 1.1
E84AVBxx1524 5.8 2.4 1.5
E84AVBxx2224 7.6 3.5 2.2
E84AVBxx3024 10.0 4.6 3.0
Note!
When the device is operated from a DC source:
ƒ the internal RFI filter is not active.
ƒ thedeviceisnotULrated.