Technical data
Rated data
Operation at rated mains voltage 400 V
4
32
EDS84ABD302 EN 4.0
Fuses and cable cross-sections
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c d L1, L2, L3 - Laying system e L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVBxx3714 C6 6 1.5 - - 10 14
30
E84AVBxx5514 C6 6 1.5 - - 10 14
E84AVBxx7514 C6 6 1.5 - - 10 14
E84AVBxx1124 C10 10 1.5 - - 10 14
E84AVBxx1524 C10 10 1.5 - - 10 14
E84AVBxx2224 C10 10 1.5 - - 10 14
E84AVBxx3024 C16 16 1.5 - - 15 14
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 V, tripping characteristic ”H”, ”K5” or ”CC”. The cable cross-sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
c Circuit breaker
d Fuse
e Fuse
Observe national and regional regulations
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c d L1, L2, L3 - Laying system e L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVBxx3714 C6 6 1.5 - - 10 14
30
E84AVBxx5514 C6 6 1.5 - - 10 14
E84AVBxx7514 C6 6 1.5 - - 10 14
E84AVBxx1124 C10 10 1.5 - - 10 14
E84AVBxx1524 C10 10 1.5 - - 10 14
E84AVBxx2224 C10 10 1.5 - - 10 14
E84AVBxx3024 C16 16 1.5 - - 12 14
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 V, tripping characteristic ”H”, ”K5” or ”CC”. The cable cross-sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
c Circuit breaker
d Fuse
e Fuse
Observe national and regional regulations