Lenze · 8400 "Position Sequencer" technology application · Software manual · DMS 1.0 EN · 07/2014 · TD05 37
4 Detailed functions of the technology application
4.4 Monitoring functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.4 Monitoring functions
4.4.1 Following error monitoring system
The difference between set position and actual position is called the following error. Ideally, the
following error should be "0". The set position is created by the internal definition of the traversing
profiles of the Motion Control Kernel. The actual position is created by the integration of the speed
supplied by the position encoder. The following error is always compensated dynamically. With an
optimum setting of the position control, only a minimum following error occurs which does not
increase continuously.
Certain processes, however, require that a defined limit as a difference between set position and
actual position is not exceeded. If it is exceeded, it may have been caused by a mechanical blocking
in the machine and the system part is not situated at the position defined at that time. In such a
case, it makes sense to activate the "Fault" error response to make the motor torqueless.
In the 8400 TopLine controller, two independent following error monitoring systems can be
parameterised:
[4-1] Two-channel following error monitoring system
&
GQ3RV6HW9DOXHBS
GQ0RWRU3RV$FWBS
DEV
$!%
$
%
W
& &
&
DEV
$!%
$
%
W
& &
E)ROORZ(UU/LP
E)ROORZ(UU/LP
Parameter
(Block)
Possible settings Info
C01215/1
(LS_MotionControl
Kernel)
0.0001 units 214748.3647 Limit for following error monitoring 1
The setting "0" deactivates following error
monitoring 1
Lenze setting: 5.0000 units
C01215/2
(LS_MotionControl
Kernel)
0.0001 units 214748.3647 Limit for following error monitoring 2
The setting "0" deactivates following error
monitoring 2
Lenze setting: 10.0000 units
C01244/2...3
(LS_MotionControl
Kernel)
0 ms 60000 Waiting time for following error monitoring 1 & 2
In order to avoid that an error is triggered by
acceleration and a narrow tolerance limit can be
nevertheless monitored at standstill in the target,
the response of the following error monitoring
system can be delayed by setting a waiting time.
Lenze setting: 0 ms
C00595/5...6
(LS_SetError_1)
Response at the activation of following error
monitoring
Subcode 5: response at the activation of following
error monitoring 1.
Subcode 6: response at the activation of following
error monitoring 2.
0No Reaction
1Fault
3 TroubleQuickStop
4 WarningLocked
5 Warning
6Information