5 Appendix: Action types for the positioning sequence control
5.2 Positioning
44
Lenze · 8400 "Position Sequencer" technology application · Software manual · DMS 1.0 EN · 07/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2 Positioning
For starting a positioning process, 50 actions of the "Positioning" type are provided.
Note!
Although 50 "Positioning" action types are provided, only 15 different profiles can be
parameterised.
The profile is entered via the parameters of the basic function "Positioning". Click the
Profile settings button to navigate to the corresponding parameterisation dialog (see
"Profile settings
" section).
Parameter Possible settings Info
Start with
(C01405/1...50)
0 Waiting function deactivated In the default setting, execution of
the profile is started immediately.
1 Sequencer input 1
(Bit 0 of wDigitalInputs)
"Wait for level": Execution of the
profile is only started when the
sequencer input selected has the
polarity set.
2 Sequencer input 2
(Bit 1 of wDigitalInputs)
... ...
16 Sequencer input 16
(Bit 15 of wDigitalInputs)
Polarity of input
(C01406/1...50)
Condition is bit state "0" State which the sequencer input
selected for the profile start must
have.
Condition is bit state "1"
Profile number
(C01407/1...50)
0 No profile executed Selection of the profile which is to be
executed.
A sequence profile can be set in the
corresponding profile parameter.
1Execute profile No. 1.
2...15 Execute profiles No. 2 ... 15