Lenze · 8400 "Position Sequencer" technology application · Software manual · DMS 1.0 EN · 07/2014 · TD05 45
5 Appendix: Action types for the positioning sequence control
5.2 Positioning
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Profile settings
A profile is described by the following profile parameters:
Monitoring time
(C01409/1...50)
0.000 s 2147480.000 If the positioning process takes
longer than the monitoring time set,
user error 1 is set. The response to
this error can be set in C00581/1
(Lenze setting: "TroubleQuickStop").
When "0.000 s" is set (Lenze setting), the
time monitoring function is deactivated.
Jump destination monit.
(C01410/1...50)
0 Sequence step Step which is executed after the
monitoring time has been exceeded.
1...100 Step 1 ... 100
Jump destination
(C01408/1...50)
0 Sequence step Step within the sequence table
which is processed after the profile
has been executed.
1...100 Step 1 ... 100
Icon Profile parameter
(Standard) profile
Profile data set (profile numbers 1 ... 15), in which the profile data are stored.
Mode (C01300/1...15)
Selection of the way in which positioning is to be carried out.
Parameter Possible settings Info