Configuration
Code table
8
8.5
8.5−61
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0906 −199.99 {0.01 %} 199.99
Function block MCTRL
l Display of the signals linked
in C0890, C0891, C0892,
C0893, C0901 and C0903
8.2−25
8.2−40
1 DIS: N−SET
2 DIS: M−ADD
3 DIS: LO−M−LIM
4 DIS: HI−M−LIM
5 DIS: I−SET
6 DIS: BOOST
C0907 0 1
Function block MCTRL
l Display of the signals linked
in C0899, C0900 and C0902
1 reserved
2 DIS: N/M−SWT
3 DIS: QSP
4 DIS: I−LOAD
C0909 speed limit 1
1 +/− 175 %
Speed limitation, function block
MCTRL
l Limitation of direction of
rotation for the speed
setpoint
8.2−25
8.2−40
2 0 ... 175 %
3 −175 ... 0 %
C0910
CFG:
VP−ADAPT
1006 FIXED100% Selection list 1 Configuration of analog input
signal, function block MCTRL
l Gain adaptation of the speed
controller
l If the gain is varying, join to
CURVE−OUT of FB CURVE
8.2−25
8.2−40
C0911 DIS: VP−ADAPT −199.99 {0.01 %} 199.99 Function block MCTRL
l Display of the signal linked in
C0910
C0912 OV delay time à − {1 ms} − Delay time of the pulse release
after an OU message
The default value can be
changed by the factor 0.5 ... 2
à depending on the type
8.2−25
8.2−40
C0940 Numerator 1 −32767 {1} 32767 Configuration of conversion
factor with numerator and
denominator, function block
CONV1
See System
Manual
(extension)
C0941 Denominator 1 1 {1} 32767
OUT[%] + IN[%] @
C0940
C0941
C0942
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block CONV1
C0943 DIS: IN −199.99 {0.01 %} 199.99 Function block CONV1
l Display of the signal linked in
C0942
C0945 Numerator 1 −32767 {1} 32767 Configuration of conversion
factor with numerator and
denominator, function block
CONV2
See System
Manual
(extension)
C0946 Denominator 1 1 {1} 32767
OUT[%] + IN[%] @
C0945
C0946
C0947
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block CONV2
C0948 DIS: IN −199.99 {0.01 %} 199.99 Function block CONV2
l Display of the signal linked in
C0947
efesotomasyon.com - Lenze