Safe standstill
Functional test
11
11.4
11.4-1
EDSVF9333V EN 3.0-06/2005
11.4 Functional test
Stop!
If the functional test leads to impermissible states at the
terminals, commissioning is prohibited!
ƒ After the installation the operator must check the ”safe standstill”
function.
ƒ The functional test must be repeated at regular intervals.
Basically, the intervals to be selected depend on the application and
the risk analysis involved as well as on the total system (inspection
interval). The inspection interval should not exceed 1 year.
Both disconnecting paths must be checked independently for their
disconnecting ability.
The safety relay K
SR
is provided with a forcibly guided feedback contact
(X11/K32, X11/K31). When the safety relay is disconnected, this feedback
must be evaluated.
X11/K32 Input ”safe standstill” X11/34 Feedback X11/K31
HIGH LOW HIGH
HIGH HIGH LOW
Monitoring can be executed continuously with a PLC. It must, however, at
least be carried out once in the defined inspection interval.
This disconnecting path must be checked while the pulse release is activated
(X11/34 = HIGH by the safety relay K
SR
.
1. Inhibit the controller (X5/28 = LOW).
2. Enter a setpoint n
set
> 0; the motor must not rotate.
It is possible to monitor the motor via visual inspection.
1. disconnecting path: Pulse
inhibit
2. disconnecting path:
Controller enable