Commissioning
Operating mode
V/f characteristic control
6
6.8
6.8.1
6.8-5
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0016 Umin boost 0.00 0.00 {0.01 %} 100.00 U
min
boost (FCODE)
z C0016=1%correspondstoa
boost of 1 % of the rated motor
voltage (C0090)
z Code is freely configurable
6.8-4
C0021 Slipcomp Æ -20.00 {0.01 %} 20.00 Slip compensation
Æ Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor
z When changing over to the
vector control mode, C0021 is
set to 0
6.11-1
8.2-25
8.2-48
C0090
Mot voltage Æ 0 {1 V} 1000 Rated motor voltage
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090
z Change of C0090 sets C0086 =
0
6.6-1
1. Select ”V/f characteristic control” mode (C0006 = 5, factory
adjustment).
2. Select V/f characteristic (C0014) if necessary
3. Enter the data of the motor nameplate.
4. If required, you can set a base frequency in C0015 which differs from
the rated motor frequency (C0089).
Adjustment