Troubleshooting and fault elimination
Display of operating data, diagnostics
Diagnostics
9
9.1
9.1.2
9.1-2
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0064 Utilisation 0 {1 %} 150 Device utilisation I×t
z Display only
z Device utilisation during the
last 180 s of operating time
z C0064 > 100 % releases
warning OC5
z C0064 >140 % limits the output
current to t he rated controller
current
8.2-25
8.2-48
C0150 Status word
Bit00 Bit08 Status Code
Read only
Decimal status word when
networked via automation
interface (AIF)
z Binary interpretation indicates
the bit states
See System
Manual
(extension)
Bit01 IMP Bit09 Status Code
Bit02
Bit10 Status Code
Bit03
Bit11 Status Code
Bit04
Bit12 Warning
Bit05 Bit13 Message
Bit06
n=0 Bit14
Bit07
CINH Bit15
9.1.2 Diagnostics
Display codes for diagnostics
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0093 DRIVE IDENT
Controller identification
z Read only
0 invalid Damaged power section
1 none No power section
9321
...
9333
9321VC
...
9333VC
Display of the controller used
C0099 S/W version
x.y
Software version
z Display only
x
y
Main version
Subversion
Description