Safe standstill
Connecting relay K
SR
11
11.3
11.3-2
EDSVF9333V EN 3.0-06/2005
Terminal assignment
Terminal Function
Bold print = Lenze setting
Level / state Electrical data
X11/K32
X11/K31
Safety relay K
SR
1. disconnecting
path
Feedback - pulse inhibit
Open contact: Pulse inhibit is
inactive (operation)
See technical data of the
safety relay K
SR
Closed contact: Pulse inhibit is
active
X11/33 coil of safety relay K
SR
Coil is not carrying any current:
Active pulse inhibit
X11/34 + coil of safety relay K
SR
Coil is carrying current: Inactive
pulse inhibit (operation)
X5/28 Controller inhibit
(DCTRL-CINH)
2. disconnecting
path
Controller enable/inhibit LOW: Controller inhibited
HIGH: Controller enabled
LOW: 0 ... +3 V
HIGH: +12 ... +30 V
Input current at +24 V:
8mA
Reading and processing
the input signals - 1/ms
(mean value)
Regulation for wiring of the terminals X11/34, X11/33, X11/K32, X11/K31,
X5/28:
Cable type Wire end ferrule Cable
cross-section
Tightening
torque
Stripping
length
Rigid 2.5 mm
2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb-in
)
5mm
Flexibl
e
with plastic sleeve 2.5 mm
2
(AWG 14)
Terminal data