Configuration
Function blocks
Master frequency ramp-function generator (DFRFG)
8
8.2
8.2.4
8.2-14
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0758
CFG: IN 1000 FIXEDPHI-0 Selection list 4 Configuration of input signal,
function block DFRFG1
z Speed/phase setpoint signal
8.2-13
C0759
cfg: qsp 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block DFRFG1
z HIGH = quick stop active
C0760
cfg: stop 1000 FIXED0 Selection list 2 Configuration of input signal,
function block DFRFG1
z HIGH = Status of the profile
generator is maintained,
setpoint is saved
C0761
CFG: RESET 1000 FIXED0 Selection list 2 Configuration of input signal,
function block DFRFG1
z HIGH = resetting the
integrators
C0764 0 1
Function block DFRFG1
z Display of the signals linked in
C0759, C0760 and C0761
1 DIS: QSP
2 DIS: STOP
3 DIS: RESET
C0765 DIS: IN -32767 {1 rpm} 32767 Function block DFRFG1
z Display of the signal linked in
C0758