Commissioning
Changing the assignment of the control terminals X5 and X6
Free configuration of analog input signals
6
6.5
6.5.3
6.5-5
EDSVF9333V EN 3.0-06/2005
Gain and offset
Setting gain (C0027) and offset (C0026) to adapt the input signal to the
application.
Input range of X6/1, X6/2
Input range C0034 Position of jumper at X3
-10 V ... +10 V C0034 = 0
6
4
2
5
3
1
+4 mA ... +20 mA C0034 = 1
6
4
2
5
3
1
-20 mA ... +20 mA C0034 = 2
Note!
Different settings in C0034 and o f X3 result in a wrong input
signal.
Adjustment