9300 Servo PLC
System blocks
2.12 MCTRL_MotorControl
2-49
L
ServoPLC EN 2.0
2.12.12 Field weakening
The field weakening range does not have to be adapted if the motor type has been selected under
C0086. All necessary parameters are set automatically.
The motor is driven in field weakening operation if
the output voltage of the controller exceeds the rated motor voltage set under C0090.
the controller cannot increase the output voltage with increasing speed because the mains
voltageandtheDC-busvoltage.
Manual field weakening
A manual field weakening is possible via
MCTRL_nFldWeak_a
for max. excitation
MCTRL_nFldWeak_a
must have +100% (= 16384) applied.
if
MCTRL_nFldWeak_a
is not assigned, the field weakening is automatically +100 % .
Stop!
The available torque is reduced by the field weakening.
2.12.13 Chopper frequency changeover
The following chopper frequencies can be set under C0018:
8 kHz for power-optimised operation ð max. power output of the controller but with audible
pulse operation.
16 kHz for noise-optimised operation ð inaudible pulse operation of the controller, however
with reduced power output (torque).
Automatic changeover between power-optimised and noise-optimised operation.
Code LCD
Possible settings
Info
o
Lenze Selection
o
C0018 fchop 1 Chopping frequency
0 16/8 kHz automa tic changeover Optimum noise reduction with auto-
matic change over to 8 kHz
18kHzsine Operation with optimum power
216kHzsine Noise-optimised operation
Automatic chopper frequency changeover
The automatic chopper frequency changeover can be used for noise-optimised operation and if the
available torque is not high enough for acceleration processes.
Condition M = f(I) Function
M<M
r16
(I
r16
) Controller operates with 16 kHz (optimum noise)
M
r16
(I
r16
)<M<M
r8
(I
r8
) Controller changes to 8 kHz (optimum power)
M>M
max8
(I
max8
) Controller operates with 8 kHz at its current limit
efesotomasyon.com - Lenze
Show/Hide Bookmarks

Table of Contents

Other manuals for Lenze Global Drive 9300 Servo PLC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze Global Drive 9300 Servo PLC Series and is the answer not in the manual?

Lenze Global Drive 9300 Servo PLC Series Specifications

General IconGeneral
BrandLenze
ModelGlobal Drive 9300 Servo PLC Series
CategoryDC Drives
LanguageEnglish

Related product manuals