2.10 DIGITAL_IO
2-36
L
ServoPLC EN 2.0
2.10 DIGITAL_IO
2.10.1 Inputs_DIGITAL
Digital inputs (module number 1)
This SB reads in the signals at the terminals X5/E1 ... X5/E5 and conditions them.
C0443
X5
Inputs_DIGITAL
1
0
C0114/1...5
E3
28
E5
E1
E4
E2
1
DCTRL-X5/28
DIGIN_bIn1_b
DIGIN_bIn2_b
DIGIN_bIn5_b
DIGIN_bIn4_b
DIGIN_bIn3_b
DIGIN_bCInh_b
Fig. 2-20 Inputs_DIGITAL
VariableName
DataType SignalType Address DIS DIS format Note
DIGIN_bCInh_b %IX1.0.0 - - Controlle r inhibit acts directly on
the DCTRL control
DIGIN_bIn1_b %IX1.0.1
DIGIN_bIn2_b
Bool binary
%IX1.0.2
DIGIN_bIn3_b
%IX1.0.3
C0443 bin
DIGIN_bIn4_b %IX1.0.4
DIGIN_bIn5_b %IX1.0.5
Electrical data of the input terminals
Terminal Use Data
X5/28 Controller enable (RFR)
LOW level: 0 ... +4 V
X5/E1
HIGH level:
+13 ... +30 V
X5/E2
Interruptible*
Input current: 8 mA per input (at 24 V)
X5/E3
*
X5/E4 TP signals, ac tual motor speed
X7 (resolver), X8 (encoder)
ree
y
assignable
< 250 µs
X5/E5 TP signal
X9 (master frequency input)
X5/39 Ground (GND) of digital inputs and outputs
• The terminal polarity of inputs E1 ... E5 can be configured under C0114.
Code LCD
Possible settings
Info
Lenze Selection
C0114 DIGIN pol Terminal polarity
0 HIGH active
1LOWactive
1 1 X5/E1
2 1 X5/E2
3 0 X5/E3
4 0 X5/E4
5 0 X5/E5