Terminal data
Rated power P
rated
kW 0.37 ... 1.5
Connecon descripon Mains c
onnecon
Connecon X100
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5
Max. cable cr
oss-secon AWG 12
Stripping length mm 8
Stripping length in 0.3
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 0.5 x 3.0
Rated power P
r
ated
kW 0.37 ... 1.5
Connecon descripon PE c
onnecon
Connecon PE
Max. cable cr
oss-secon mm² 6
Max. cable cr
oss-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 2
Tightening torque lb-in 18
Required tool T20
Rated power P
r
ated
kW 0.37 ... 1.5
Connecon descripon Motor c
onnecon
Connecon X105
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5
Max. cable cr
oss-secon AWG 12
Stripping length mm 8
Stripping length in 0.3
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 0.5 x 3.0
Fusing data
A residual current device (RCD) is oponal.
Inverters Fuse Circuit breaker RCD
Characterisc
Max. rated
curr
ent
Characterisc
Max. rated
current
Type
A A mA
I95AE137D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE155D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE175D gG/gL, gRL 16 B 10 ≥30 Typ B
I95AE215D gG/gL, gRL 16 B 16 ≥30 Typ B
Electrical ins
tallaon
Mains connecon
1-phase mains connecon 230/240 V