EasyManua.ls Logo

Lenze i950 Series - Terminal Data; Fusing Data

Lenze i950 Series
188 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Terminal data
Rated power P
rated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Mains c
onnecon
Connecon X100
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5 16
Max. cable cr
oss-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool 0.5 x 3.0 0.8 x 4.0
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon PE c
onnecon
Connecon PE
Max. cable cr
oss-secon mm² 6 16
Max. cable cr
oss-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.4
Tightening torque Nm 2 3.4
Tightening torque lb-in 18 30
Required tool T20 PZ2
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Motor c
onnecon
Connecon X105
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5 16
Max. cable cr
oss-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool 0.5 x 3.0 0.8 x 4.0
Fusing data
A residual current device (RCD) is oponal.
Inverters Fuse Circuit breaker RCD
Characterisc
Max. rated
curr
ent
Characterisc
Max. rated
current
Type
A A mA
I95AE137D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE155D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE175D gG/gL, gRL 16 B 10 ≥30 Typ B
I95AE215D gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE222C gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE240C gG/gL, gRL 50 B 50 ≥300 Typ B
I95AE255C gG/gL, gRL 50 B 50 ≥300 Typ B
Electrical ins
tallaon
Mains connecon
3-phase mains connecon 230/240 V
141

Table of Contents

Related product manuals