X82 Specicaon Unit Min. Typ. Max.
CLA, CLB PLC output, IEC-61131-2, 24 V DC, 50 mA
Low signal output voltage V 0 +0.8
High signal output voltage V +17 +24 +30
Output current mA 60
Cable capacity nF 100
Cable resistance of a passive sensor 200
O1A, O1B PLC output, IEC-61131-2, 24 V DC
Low signal output voltage V 0 0.8
High signal output voltage V 17 24 30
Output current mA 500
Cable capacity nF 100
Cable resistance 200
GS Reference potenal for terminals
CLA, CLB
O1A, O1B
24S
24S Supplies the clock outputs and the safe output via a
safely separated power supply unit (SELV/PELV)
V 18 24 30
Input current mA 1100
GSI Reference potenal terminals IRS/IRL/AIS/IRS
IRS
IRL
AIS
AIE
PLC input, IEC-61131-2, 24 V, type 1
Low signal input voltage V -3 0 5
High signal input voltage V 15 24 30
Input current mA 2 15
Input capacitance nF 3.5
Input delay (oper
ang me) for AIE and AIS s 0.3 10
The inputs and outputs must be wired with shielded cables.
X83 Specicaon Unit Min. Typ. Max.
I1A, I1B
I2A
, I2B
I3A, I3B
I4A, I4B
PLC input, IEC-61131-2, 24 V, type 1
Low signal input voltage V -3 0 5
High signal input voltage V 15 24 30
Input current mA 2 15
Input capacitance nF 3.5
Repeat rate of test pulses ms 50
GI1
GI2
GI3
GI4
Reference potenal for terminals
I1A ... I4B
The inputs and outputs must be wired with shielded cables.
Connecon descripon SOC
Connecon X82 X83
Connecon type Pluggable Pluggable
Max. cable cr
oss-secon mm² 1.5 1.5
Max. cable cr
oss-secon AWG 16 16
Stripping length mm 9 9
Stripping length in 0.35 0.35
Required tool 0.4 x 2.5
Electrical ins
tallaon
Funconal safety