Commissioning
Vector control
7
EDK82MV371 DE/EN/FR 6.0
105
L
12. Activate the control mode "vector
control" (C0014 = 4)
Lenze setting: Linear V/f
characteristic control (C0014 =
2)
d ABbc
p
SHPRG
Para
Code
Menu
0014
00
4
Vector-Ctrl
9371BC008
13. Adapt the voltage/current range
for the analog setpoint selection
(C0034)
Lenze setting: −0−,
(0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
wx
0
000
abcd e
mno
p
qr
Hi
Lo
1
j gfkih PS
0034
Set the DIP switch on the
standard I/O to the same
range (see Mounting
Instructions for the
standard I/O)
14. Enter the motor data See motor nameplate
A Rated motor speed (C0087)
Lenze setting: 1390 rpm
B Rated motor current (C0088)
Lenze setting: Depending on the
controller
Enter the value for the
motor connection type
(star/delta) selected!
C Rated motor frequency (C0089)
Lenze setting: 50 Hz
D Rated motor voltage (C0090)
Lenze setting: Depending on the
controller
Enter the value for the
motor connection type
(star/delta) selected!
E Motor−cos (C0091)
Lenze setting: Depending on the
controller