The following instructions apply to controllers equipped with a standard−I/O
function module and a three−phase AC motor which has been selected
accordingly.
1. Connect the keypad
2. Ensure that controller inhibit is
active after mains connection
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in "Disp" mode
after approx. 2 s and indicates
the output frequency (C0050)
000
000
abcd e
mno
p
qr
Hi
Hz
Lo
1
j
gfkih PS
0050
The menu USEr is active
5.
Go to the menu ALL
6. Change to the mode to
configure the basic settings for
your drive
000
000
a
bcd e
mno
p
qr
Hi
Hz
Lo
1
j gfkih PS
0050
z
y
wx
Blinking on the display:
0050
7. Adapt the terminal configuration
to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpoint
selection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
z
y
wx
0
000
a
bcd e
mno
p
qr
Hi
Lo
1
j gfkih PS
0007
8. Set the minimum output
frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9. Set the maximum output
frequency (C0011)
Lenze setting: 50.00 Hz
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
+t
ir
@
C0011
f
2
* f
1
t
ir
= acceleration time
wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+t
if
@
C0011
f
2
* f
1
t
if
= deceleration time
wanted