6 Commissioning
6.7 "Shared Device" function
52
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.7 "Shared Device" function
This function is available from SW version 2.10!
The "Shared Device" function of PROFINET IO provides the opportunity to access an IO device with
two Controllers. The Lenze application for "Shared Device" is the easy assignment of data to a safety
controller and an IO controller (in fig. [6-2]
the separation of the grey and yellow area).
[6-2] "Shared Device" function
In order to use the "Shared Device" function, import the GSE file "GSDML-V2.3-Lenze-9400PN200-
20130424.xml" into the PROFINET configuration tool of the respective controller manufacturer.
The IO data or safety data is permanently assigned to the data slots.
• Slot 1 is always the grey area (IO controller)
• Slot 2 is always the yellow area (safety controller)
Note!
The data assignment to the corresponding Controller is carried out in the configuration
tool. For this purpose, follow the descriptions in the documentation of the tool.
Settings in the E94AYCER communication module are not required.