Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17 35
6 Commissioning
6.3 Setting the station name
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the station name
The station name currently used is shown in code C13864 / C14864.
The station name ...
• is required for unambiguous addressing of the Servo Drive 9400 by the I/O controller.
• can either be assigned by the I/O controller via PROFINET or set manually in the »Engineer«.
• has to be allocated in accordance with the PROFINET specification:
• 1 or several labels separated by ".".
• Max. length per label: 63 characters
• Max. total length: 240 characters
• Permissible characters: [a ... z], [0 ... 9], [.], [-]
• Labels must not begin or end with [-].
• Prohibited syntax:
• "n.n.n.n" (n = 0 ... 999)
• "port-xyz" (x, y, z = 0 ... 9)
• "port-xyz-abcde" (a,b,c,d,e,x,y,z=0...9)
Note!
• The "node blinking" PROFINET function by means of which an accessible field service
can be identified is supported. While the function is being executed, the red LED ME
(Module status displays
( 80)) is blinking.
• Operation of PROFINET requires a valid station name.
• In case of impermissible settings, the red LED BE (Fieldbus status displays
( 81)) is
blinking and the error message PROFINET: Invalid station name [0x00c86532]
( 88)
is output. The communication module then continues to work internally with the
deleted name.
• If the station name is assigned by the IO controller via PROFINET or via the PROFINET
configurator of the »Engineer«, changes will become effective immediately.