13 Error messages
13.2 Possible causes and remedies
88
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: Invalid module configuration [0x00c86430]
PROFINET: Invalid READ.request during parameter access [0x00c86501]
PROFINET: Invalid WRITE.request during parameter access [0x00c86502]
PROFINET: Data output status bad [0x00c86503]
PROFINET: Invalid station name [0x00c86532]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
A module or submodule does not comply with the
configuration of the Siemens »STEP7« project.
Check/correct configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
During the parameter access to data set 47, the
controller has sent an invalid READ.request.
When reading back the data, the IO Controller has
requested a data length (number of data bytes) that is
to small.
Check/correct configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
During the parameter access to data set 47, the
controller has sent an invalid WRITE.request.
When reading back the data, the IO Controller has
requested a data length (number of data bytes) that is
to small.
Check/correct configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Output data invalid.
Connection to the Siemens Controller has been
interrupted.
Check cables and terminals.
Plug in the network cable on the PROFINET terminal
X241/X242.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Station name is not PROFINET-compliant. Use a PROFINET-compliant station name.
Setting the station name
( 35)