Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17 49
6 Commissioning
6.5 Establishing an online connection via PROFINET with the Lenze »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.5 Establishing an online connection via PROFINET with the Lenze »Engineer«
This functionality will only be supported from software version V01.30.05 onwards.
[6-1] Online connection via PROFINET with the Lenze »Engineer«
In order to establish an online connection between the »Engineer« and the inverter, the inverter has
to have an IP address (see Setting the IP configuration
( 37)).
Note!
To ensure perfect operation of cyclic PROFINET communication, online access with the
»Engineer« must be effected via a PROFINET switch.
The PROFINET switch integrated in the communication module can execute cyclic
PROFINET communication prior to normal TCP/IP communication. In the case of
PROFINET this is effected via the VLAN identification in the Ethernet frame.