Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17 89
13 Error messages
13.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: Invalid IP parameters [0x00c86533]
PROFINET: Safety communication timeout [0x00c86610]
PROFINET: Safety parameter timeout [0x00c86611]
PROFINET: Safety init error [0x00c86612]
PROFINET: Safety connect error [0x00c86613]
PROFINET: Internal error [0x00c86650]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Incorrect IP parameters (IP address, subnet mask,
gateway address).
Correct IP parameters.
Setting the IP configuration
( 37)
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Communication to the SM30x safety module is
disrupted.
Check if the SM30x safety module is plugged in and
supplied with voltage.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The SM30x safety module does not respond to a
PROFISafe parameterisation frame within a given time
interval (200 ms).
Check if the SM30x safety module is plugged in and
supplied with voltage.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Communication to the SM30x safety module could not
be initialised correctly.
Check whether the user data length configured in the
PROFINET IO controller for the PROFIsafe data matches
the SM30x safety module used.
Configuring the PROFINET IO controller
( 33)
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Communication to the I/O controller is disrupted. Check if the SM30x safety module is plugged in and
supplied with voltage.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Send communication module together with a
description of the fault to Lenze.