14 Parameter reference
14.3 Parameters of the communication module for slot MXI2
106
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14861
C14862
C14864
Parameter | Name:
C14861 | Bus status
Data type: UNSIGNED_16
Index: 9714 = 0x25F2
Display of the current bus status
Querying the current bus status
( 83) (representation of the bit-coded display)
Display list
0x0000 Init
0x0030 No Data Exchange
0x0020 Data Exchange / Process Data Valid
0x0010 Data Exchange / Process Data Invalid
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14862 | Data cycles per second
Data type: UNSIGNED_32
Index: 9713 = 0x25F1
Display of the data cycles per second (independent of data changes)
Note: This code will not be supported anymore from SW version 2.10 for reasons related to the system.
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14864 | Active station name
Data type: VISIBLE_STRING
Index: 9711 = 0x25EF
Display of the station name actively used by the inverter.
The active station name may differ from the contents of code C14899
, depending on whether the station name was
changed via the fieldbus or the parameter (C14899
).
Setting the station name
( 35)
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT