9 Parameter data transfer
9.3 Writing parameters to the inverter
72
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter response to a correctly executed write request
Parameter response after write error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identification Axis Number of indices
0xXX 0x02 0x00 0x01
(mirrored) Parameter has been written (mirrored) 1 index
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identification Axis Number of indices
0xXX 0x82 0x00 0x01
(mirrored) Parameter has not been written (mirrored) 1 index
Byte 5 Byte 6
Format Number of values
0x44 0x01
Fault Error code without additional
information
Byte 7 Byte 8
Error code
High byte Low byte
For the meaning see the chapter "Error information
(error)" ( 73)