CMVETH01B 16
Commissioning
SMVector Programming & Configuration
Basic Setup
Get/Set Parameter
Basic Setup
IP Settings
Rotation
Commissioning
Start Control Source
Read
Write
1 - Forward and Reverse
0 - Local Keypad
No.
P100
P112
P121
P122
P123
Name Selection / Setting
TB-13A Input Function
TB-13B Input Function
TB-13C Input Function
9 - Network Enable
10 - Reverse Rotation
8 - Control Select
Figure 12: SMV Commissioning - Basic Setup
SMVector Programming & Configuration
Get/Set Parameter
Get/Set Parameter
Basic Setup
IP Settings
Parameter Number
Commissioning
Parameter Value
Read Write
0
0
Figure 13: SMV Commissioning - Get/Set Parameter
The web server's write access ability can be disabled for security purposes by setting P492 to "1".
TIP!
To ensure that the drive is network control ready, open the Get/Set Parameter. Write a value of 97 to register 65 to
start the drive. Write a value to P61 (ex 212 = 21.2Hz).Then write a value of 0 to 65 to stop the drive.
WARNING!
Make sure it is safe to operate the driven equipment prior to starting the SMV drive from the network. Damage to
equipment and/or injury to personnel can result.