Diagnostics
8 Diagnostics
8.1 Faults
In addition to the normal drive fault codes, the additional codes listed in Table 23 may be generated by the
option module during a fault condition.
Table 23: Fault Codes
Fault Code Definition Remedy
F.ntF Module Time-out Module to drive communications time out.
Check cable and connection between drive and option module.
F.nF1 NetIdleMode
(Idle event received in I/O message header)
Refer to section 9.1, Parameter P431
F.nF2 NetFaultMode
(Loss of I/O connection Exclusive Owner)
Refer to section 9.1, Parameter P432
F.nF3 Network Fault triggered via Control
Supervisor Object 0x29-1-17
Refer to Section 9.2.8, Control Supervisor Object
F.nF4 Explicit message timeout reaction Triggered by Explicit message expected packet rate time-out, 'F.nF4'
Refer to section 9.1, Parameter P433
F.nF5 Action on overall Ethernet timeout
(no explicit or I/O messages received or Web
Server access)
Trigger by expiration of timer monitoring all messages received by the
module (refer to P435 for setup)
Refer to section 9.1, Parameter P434
F.nF6 Explicit message timeout reaction Expiration of overall explicit message timer 'F.nF6'.
Refer to section 9.1, Parameter P433
F.nF7 Overall I/O Message Timeout Expiration of overall I/O message timer 'F.nF7'.
Refer to section 9.1, Parameter P432
8.2 Troubleshooting
Table 24: Troubleshooting
Symptom Possible Cause Remedy
No communications
from the option
module
Module is not initialised Check the drive to module connection.
Check P400 and P402.
Incorrect EtherNet/IP settings Check P410 - P421.
If unsure of setting, reset EtherNet/IP parameters to
factory default using P403.
Power cycle drive after changing IP address setting
or use P408.
Improper wiring Check wiring between the EtherNet/IP network and
communication module.
Ensure that the terminal block is properly seated.
Check connection between module and drive.
EtherNet/IP write
commands are
ignore or return
exceptions
"Network enabled" terminal is
either open or not configured
Configure one of the input terminals (P121, P122 or P123)
to "Network Enabled" function (selection 9) and close the
corresponding contact.
Drive does not
change direction to
REVERSE
Parameter P112 is set to 0
(Forward Only)
Set drive parameter P112 to 1 to enable Forward &
Reverse direction