55 CMVETH01B
Advanced Features
7 Advanced Features
7.1 Option Module Advanced Parameters
7.1.1 Module Revision
P401 - Module Revision
Default: 5.x.x Range: 5.0.0 - 5.9.9
Access: RO Type: Integer
Display reads 5.x.x where: 5 = EtherNet/IP Module and x.x = Module Revision
7.1.2 Module Status
P402 - Module Status
Default: N/A Range: 0 - 7
Access: RO Type: Integer
Table 21: Module Status
P402 Value Description P402 Value Description
0 Not Initialised 4 Error: Failed Initialisation
1 Initialisation: Module to EPM 5 Error: Time Out
2 Initialisation: EPM to Module 6 Error: Module Mismatch (P401)
3 Online 7 Error: Protocol Mismatch (P400)
7.1.4 Module Time-out Action
P404 - Module Time-out Action
Default: 3 Range: 0 - 3
Access: RW Type: Integer
This parameter controls the action to be taken in the event of a Module-to-Drive time out. The Time-out
period is fixed at 200 ms.
Table 22: Module Time-out Action
P404 Value
0 1 2 3
Description
No Action Stop (controlled by P111) Quick Stop
Fault F.ntf
7.1.5 Initialize Ethernet/IP Settings
P408 - Initialize Ethernet/IP Settings
Default: 0 Range: 0 - 1
Access: RW Type: Integer
This parameter reinitializes the Ethernet/IP network parameters. 0 = No action. 1 = Reset communication.
7.1.6 Module Firmware
P494 - Module Firmware
Default: N/A Range: 1.00 - 99.99
Access: RO Type: Integer
Displays the module firmware revision in the format of xx.yy, where: xx = Major version and yy = Minor
version