Cyclic Data Access
5.6 Output Assemblies
5.6.1 Output Assembly 20 - Basic Speed Control
Word 0
Bit 0 0 = NOT Run Forward
1 = Run Forward
Bit 1 Reserved
Bit 2 Fault reset on transition from 0 to 1
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Word 1
Speed in RPMs (max 32767)
• RPM is calculated based on P305 and P304
• Example 1 (P305 = 1750 RPM, P304 = 60 Hz):
Requested speed command 25.0 Hz = 25.0 x 1750/60 = 729 = 0x02D9
NOTE
To use this Output assembly (20) Network Control and Network Reference must be set using explicit
communication by writing into the control word at NetId 65 the bit configuration of this word matches the
WORD 0 of output assembly 100.
5.6.2 Output Assembly 21 - Extended Speed Control
Word 0
Bit 0 0 = NOT Run Forward
1 = Run Forward
Bit 1 0 = NOT Run Reverse
1 = Run Reverse
Bit 2 Fault reset on transition from 0 to 1
Bit 3 Reserved
Bit 4 Reserved
Bit 5 0 = Local Control
1 = Network Control
Bit 6 0 = Local Speed reference
1 = Network Speed reference
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Word 1
Speed in RPMs (max 32767)
• RPM is calculated based on P305 and P304
• Example 1 (P305 = 1750 RPM, P304 = 60 Hz):
Requested speed command 25.0 Hz = 25.0 x 1750/60 = 729 = 0x02D9
NOTE
In order to Start/Stop the drive via network control, bit 5 of Word 0 must be set in this assembly.
In order to control the speed via network communications, bit 6 of Word 0 must be set in this assembly.