15 CMVETH01B
Commissioning
4.1.2 Configuring the SMVector Drive
Once the PC's IP address is configured, open up a standard web browser and enter the drive's IP address
(default: 192.168.124.16) into the Address field. If the drive has been given a new IP address, then that
IP address must be the one entered in the web browser. Press [Enter]. The SMVector Programming and
Configuration page will open. The Commissioning menu on the left-hand side allows the user to navigate
through and configure the drive setup and diagnostic parameters.
Table 4: Commissioning Menu Folders
Folder
IP Settings Basic Setup Get/Set Parameter
Configurable
Parameters
MAC Address P100 (Start Control Source) Parameter Number
IP Address P112 (Rotation) Parameter Value
Network Mask P121 (TB-13A Input Function)
Gateway Address P122 (TB-13B Input Function)
Multicast Address P123 (TB-13C Input Function)
In the [IP Settings] window, to select a new IP address, click [Write]. Type a value in the IP address octet
windows. Then click [Apply Settings]. Power cycle the drive in order for the new IP address to take effect.
SMVector Programming & Configuration
IP Settings
Get/Set Parameter
Basic Setup
IP Settings
IP Address
Commissioning
MAC Address
Read Write
168
192
Network Mask
Gateway Address
Multicast Address
Apply Settings
124 16
.
. .
...
.
.
.
.
.
.
255
255
255
0
192
168 124 1
239
64
2
224
00-0c-61-80-00-00
Figure 11: SMV Commissioning - IP Settings
WARNING!
Make sure it is safe to operate the driven equipment prior to starting the SMV drive from
the network. Damage to equipment and/or injury to personnel can result.