CMVETH01B 40
Cyclic Data Access
NOTE 1: Digital Input/Output State
Word – Digital Input/Output State
Bit 0
Bit 1
Bit 2 Output Fault
Bit 3 Fast Current Limit State
Bit 4 TB1 ON
Bit 5
Bit 6 TB13A
Bit 7 TB13B
Bit 8 TB13C
Bit 9 TB14 Out State
Bit 10 Relay State
Bit 11 Charge Relay
Bit 12 Assertion level
Bit 13
Bit 14
Bit 15
Input Assembly 106 Options
In addition to all drive parameters that can be specified in Parameters P450 ... P453, there are additional
status and real-time values (range 1-12) that can be specified.
P45x = 1, SMV Status Word
P45x = 2, Actual Frequency
P45x = 3, Lenze C150 Status Word
P45x = 4, Actual Speed in RPMs
P45x = 5, Auxiliary Status
P45x = 6, Drive RUN Status
P45x = 7, Drive Fault Status
P45x = 8, Digital I/O Status
P45x = 9, Analog 0-10V Input
P45x = 10, Analog 4-20mA Input
P45x = 11, Actual PID Setpoint
P45x = 12, Actual PID Feedback