Technical data
General data
2
EDK71MMXXX-020 DE/EN/FR 1.0
11
L
Conformity CE Low-Voltage Directive (73/23/EEC)
EMC Directive (93/68/EEC)
Standards DIN EN 60947-4-2 Semiconductor motor control devices and starters for AC
voltage
Approvals UL 508 Underwriter Laboratories (File-No. E132659)
Power Conversion Equipment
(in preparation)
Vibration resistance Acceleration resistant up to 4g (Germanischer Lloyd, general conditions)
Climatic conditions Class 3K3 to EN 50178 (without condensation, average relative humidity 85
%)
Degree of pollution VDE 0110 part 2, pollution degree 2
Permissible
Transport -25°C...+70°C
temperature ranges
Storage -25°C...+60°C
Operation Motor mounting: -25 °C ... +60 °C
Wall mounting: -25 °C ... +40 °C
Permissible installation
height
0 ... 4000 m amsl
reduce the rated output current by 5%/1000 m above 1000 m amsl
Mounting positions Every mounting position is permissible
Free space
above 100 mm
to the sides 100 mm
EMC8. Compliance with EN 61800-3/A11
Noise emission Compliance with limit value class B to EN 60947-4-2
Discharge current to PE (to
EN 50178)
<3.5mA
Type of protection9. IP 55; NEMA 1: Protection against contact
IP 65; NEMA 4 (with protection cover over AIF interface)
Protection measure against Motor overtemperature (input for PTC or thermistor, I
2
t monitoring)
Insulation of control circuits Safe mains disconnection:
Double/reinforced insulation to EN 50178
Insulation strength Overvoltage category III to VDE0110