Device parameters and interfaces
78 BPS 34 Leuze electronic
Input data
None
Output data
None
8.1.7.20 Module 19: Service
Description
The "service" function is used to reset the parameter set of the BPS 34 to default settings.
This reset only occurs directly in the BPS 34. After the reset function has been activated, the
device carries out a reset and is freshly configured on the PROFIBUS. This results in the
reactivation of all modules and parameter settings selected in the PROFIBUS project.
Parameters
None
Input data
Output data
Internal address
of module 18
Position
tolerance time
address 0
Delay error
output
address 2
14 00 32 01
Input data Description Rel.
addr.
Data
type
Value range Default Unit CR to
module
Status byte
Shows the state of the reset to
factory settings.
0
unsign
8
0x00: Not active or suc-
cessfully concluded
0xFF: Reset active
0xF1: EEPROM access error
0x00 ––
Input data length: 1 byte
a
Output
data
Description Rel.
addr.
Data
type
Value range Default Unit CR to
module
Factory
settings
Reset of parameters to factory
settings.
0.0 Bit
0 -> 1: Reset the parameters
1 -> 0: Normal operation
0 ––
Output data length: 1 byte
b