The pump is designed to require little user maintenance. Observe the
following guidelines when carrying out maintenance on the pump:
▪ Make sure the maintenance is done by a suitably trained and supervised▪
technician. Obey local and national safety requirements.
▪ Make sure the maintenance technician is familiar with the safety▪
procedures which relate to the products processed by the pumping
system.
▪ Check that all the required parts are available and are of the correct type▪
before starting work.
9.2Maintenance plan
More frequent maintenance may be required if the pump is used to pump
aggressive gases or vapours, such as solvents, organic substances and
acids, or if the pump is operated continuously at the higher end of its
operating temperature.
Table 18 Maintenance plan
Operation
Frequency
(months)
Service
indicator
1-phase
Hours
indicators
1-phase
3-phase
Section
reference
Inspect and clean the
inlet strainer
12 No 8760
on page 57
Inspect and clean the
external fan cover if
required
12 No 8760
on page 58
Check the pump
performance
30 Yes 21900
on page 58
Replace the tip-seal
30 or when
needed
Yes 21900
on
page 58
Replace the pump
bearings
60 Yes 43800
on page 58
Replace the pump
controller
120 Yes 87600
on page 59
Electrical safety check 60 No 43800
on
page 60
9.3Inspect and clean the inlet strainer
Whenever the pump is disconnected from the vacuum system, or on an
annual basis, we recommend:
▪ Removing the inlet strainer from the pump inlet and remove any debris▪
that may have accumulated. Refer to
.
▪ Inspecting the inlet strainer and if necessary, clean it with a cleaning▪
solution suitable for the substances pumped. Ret the inlet strainer
before reconnecting the pump to the vacuum system. Refer to
on page 28.
300668736_002_C7 - © Leybold 57
Maintenance